Unshielded Twisted Pair cable (UTP), 8/10/12/16 pairs, Solid, Indoor, Category 5

Unshielded Twisted Pair cable (UTP), 8 pairs, Solid, Indoor, Category 5
Unshielded Twisted Pair Cable UTP, 8 pairs

Unshielded Twisted Pair cable (UTP), 12 pairs, Solid, Indoor, Category 5
Unshielded Twisted Pair Cable UTP, 12 pairs

Specification
Meets ANSI/EIA/TIA-568-A and ISO/IEC 11801
Fire protection CM
The cable meets UL 1581 VW-1 fire safety standard and IEC 60332.1

Description
Unshielded copper cable, 8/10/12/16 pairs, conductor insulation: PVC
Cable is used for indoor installation

Materials
Conductive material: wire made of soft annealed electrolytic copper
Conductor insulation: polyolefin
The cable jacket: PVC

Electrical characteristics
Frequency, MHz Max attenuation,
dB/100 m (dB/100 ft)
Min PS-NEXT losses, dB Low value PS-ACR,
dB/100 m (dB/100 ft)
0.772 1.8 (0.55) 64 62.2 (19.0)
1.0 2.0 (0.6) 62 60.0 (18.3)
4.0 4.1 (1.3) 53 48.9 (14.9)
8.0 5.80 (1.8) 48 42.2 (12.9)
10.0 6.5 (2.0) 47 40.5 (12.3)
16.0 8.2 (2.5) 44 35.8 (10.9)
20.0 9.3 (2.8) 42 32.8 (10.0)
25.0 10.4 (3.2) 41 30.6 (9.3)
31.25 11.7 (3.6) 39 28.3 (8.6)
62.5 17.0 (5.2) 35 18.0 (5.5)
100.0 22.0 (6.7) 32 10.0 (3.0)


Max. direct-current resistance at 20C (68F) 93.8 Ohm/km (151.3 Ohm/mile)
Resistance unbalance 3%
Resistance at the frequency of 1-100 MHz 100 15 Ohm
Capacity at the frequency of 1 kHz 50 4 pF/m (15.3 1 pF/ft)
Capacitive unbalance at the frequency of 1 kHz 3300 pF/km (5322.6 pF/mile)
Min. unbalance losses at the frequency of 64 kHz 43 dB
Maximum voltage 300 V
Insulating strength 1000 V RMS
Propagation velocity 68%
Max. propagation delay
at the frequency of 1 MHz
at the frequency of 10 MHz
at the frequency of 100 MHz

5.7 ns/m (1.74 ns/ft)
5.4 ns/m (1.64 ns/ft)
5.3 ns/m (1.61 ns/ft)
Derivation propagation delay 35 ns/100 m (10.67 ns/100 ft)
Min. insulating resistance 5 GOhm/km (8.05 GOhm/mile)

Twisted Pair cable (UTP) 8 pairs 8 pairs
1 Jacket
2 - Protective skin
3 - Solid twisted pair
4 - Main load-bearing element
Technical characteristics
Conductor diameter: 0.51 mm (0.02") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 7.2 mm (0.283")
Jacket thickness: 0.7 mm (0.027")
Minimum bend radius: 6 outer cable diameters
Pulling strength: 500 N Breaking strength: 600 N Installation temperature: -5°C - +40°C (+23°F - +104°F)
Operating temperature: -20°C - +60°C (-4°F - +140°F)
Weight per 1000 ft (304.8 m): 18.288 kg (40.3 lbs)
Standard package: 1000 m (3280 ft)

Twisted Pair cable (UTP) 10 pairs 10 pairs
1 Jacket
2 - Rip-cord
3 - Protective skin
4 - Solid twisted pair
5 - Main load-bearing element
Technical characteristics
Conductor diameter: 0.51 mm (0.02") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 7.6 mm (0.299")
Jacket thickness: 0.8 mm (0.032")
Minimum bend radius: 6 outer cable diameters
Installation temperature: -5°C - +50°C (+23°F - +122°F)
Operating temperature: -20°C - +60°C (-4°F - +140°F)
Weight per 1000 ft (304.8 m): 21.884 kg (48.2 lbs)
Standard package: 1000 m (3280 ft)

Ordering
UTPXXM-C5-SOLID-INDOOR Unshielded Twisted Pair Cable UTP, 8/10/12/16 pairs, solid, indoor, category 5

XX - quantity of pairs: 8, 10, 12, 16 pairs